Configurazione di un UPS
Collegare l'ups seriale su COM1 (/dev/ttyS0)
Installare il software di gestione
apt-get install apcupsd
Verificare la porta a cui si è collegato l'UPS
L'elenco delle porte seriali lo si può ottenere con:
dmesg | grep ttyS
Si ricorda che:
COM1=ttyS0 COM2=ttyS1
Nel caso si correga nel file /etc/apcupsd/apcupsd.conf:
DEVICE /dev/ttyS0
Testare la comunicazione con l'ups:
apctest
Attendere anche sino ad 1 minuto:
2005-05-23 15:08:38 apctest 3.10.16 (04 November 2004) debian Checking configuration ... Attached to driver: apcsmart sharenet.type = DISABLE cable.type = CUSTOM_SMART You are using a SMART cable type, so I'm entering SMART test mode mode.type = SMART Setting up the port ... Creating the device lock file ... Hello, this is the apcupsd Cable Test program. This part of apctest is for testing Smart UPSes. Please select the function you want to perform. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit Select function number: 1
Inserire 1
I am going to run through the series of queries of the UPS that are used in initializing apcupsd. Simulating UPSlinkCheck ... Wrote: Y Got: SM Attempting to use smart_poll() ... Sent: Y Got: SM Good -- smart_poll() works!. Going to ask for valid commands... Protocol version is: 3 Alert characters are: !$%+?=#| Command characters are: ^A^N^Z')+-89>@ABCDEFGKLMNOPQRSUVWXYZabcefgjklmnopqrsuxyz^M Now running through apcupsd get_UPS capabilities(). NA indicates that the feature is Not Available UPS Status: 08 Line quality: FF Reason for last transfer to batteries: T Self-Test Status: NO Line Voltage: 223.2 Line Voltage Max: 224.6 Line Voltage Min: 223.2 Output Voltage: 223.2 Batt level percent: 100.0 Batt voltage: 27.54 UPS Load: 012.3 Line freq: 50.00 Runtime left: 0104 UPS Internal temp: 029.2 Dip switch settings: NA Register 1: 00 Register 2: 00 Register 3: 00 Sensitivity: H Wakeup delay: 000 Sleep delay: 090 Low transfer voltage: 208 High transfer voltage: 253 Batt charge for return: 00 Alarm status: 0 Low battery shutdown level: 02 UPS Name: UPS_IDEN UPS Self test interval: 336 UPS manufacture date: 02/02/05 UPS serial number: AS0506111930 Date battery replaced: 02/02/05 Output voltage when on batteries: 230 Nominal battery voltage: 024 Percent humidity: NA Ambient temperature: NA Firmware revision: 600.3.I Number of external batteries installed: 000 Number of bad batteries installed: NA UPS model as defined by UPS: FWI UPS EPROM capabilities string: uD43127130133136uA43108110112114uI43253257261265uM43225229233237lD43106103100097lA43092090088086lI43208204200196lM43182178174170e47200153045607590oD13120oA13100oI33230240220oM13208s431HMLq4820205081114172023p483090180270360450540630000k4310TNr483000060120180240300360420E443336168ON OFF The EPROM string is 286 characters long! Hours since last self test: NA That is all for now. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit Select function number: 7 2005-05-23 15:14:32 End apctest.
Abilitazione del Demone
vi /etc/default/apcupsd ... ISCONFIGURED=YES ...
Avviare il demone:
/etc/init.d/apcupsd start
Verifica del rilevamento caduta di tensione:
tail -f /var/log/apcupsd.events
Mon May 23 15:22:31 CEST 2005 apcupsd 3.10.16 (04 November 2004) debian startup succeeded Mon May 23 15:23:09 CEST 2005 Power failure. Mon May 23 15:23:11 CEST 2005 Running on UPS batteries. Mon May 23 15:23:36 CEST 2005 Mains returned. No longer on UPS batteries. Mon May 23 15:23:36 CEST 2005 Power is back. UPS running on mains.